No |
Items |
Unit |
Data |
|||||||
1 |
Rated voltage |
kV |
126 |
145 |
||||||
2 |
Rated P.F. withstand voltage (1min) |
To ground |
230 |
275 |
||||||
Between gaps |
265 |
315 |
||||||||
3 |
Rated lightning impulse withstand voltage |
To ground |
550 |
650 |
||||||
Between gaps |
630 |
750 |
||||||||
4 |
Rated P.F. withstand voltage under SF6 zero gauge pressure(5min.) |
kV |
95 |
|||||||
5 |
Rated frequency |
Hz |
50 |
|||||||
6 |
Rated current |
A |
3150 |
|||||||
7 |
First pole factor |
|
1.5 |
|||||||
8 |
Rated short-circuit breaking current |
kA |
40 |
31.5 |
||||||
9 |
Rated short-circuit making current |
100 |
80 |
|||||||
10 |
Rated short-time withstand current |
40 |
31.5 |
|||||||
11 |
Rated peak withstand current |
100 |
80 |
|||||||
12 |
Rated short circuit duration |
s |
4 |
|||||||
13 |
Rated out of phase breaking current |
kA |
10 |
|||||||
14 |
Short-line fault breaking current |
36 |
30 |
No |
Items |
Unit |
Data |
||
15 |
Rated line charge breaking current |
A |
31.5 |
||
16 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
||
17 |
Opening time |
ms |
30 3 |
||
18 |
Closing time |
75 8 |
|||
19 |
Closing/opening time |
60 |
|||
20 |
Main circuit resistance |
u |
40 |
||
21 |
Rated SF6 gas pressure (20 gauge pressure) |
Mpa |
0.6 |
||
22 |
Alarm/locking pressure (20 gauge pressure) |
0.55/0.50 |
|||
23 |
Annual gas leakage rate of SF6 gas |
% |
1 |
||
24 |
Water content of gas |
ppm(v) |
150 |
||
25 |
Mechanical life |
time |
6000 |
||
26 |
Radio interference level |
uV |
500 |
||
27 |
Creepage distance |
To ground |
mm |
3150 |
3625 |
Between gaps |
3150 |
3625 |
|||
28 |
SF6 gas weight per circuit breaker |
kg |
10 |
||
29 |
Unit weight of circuit breaker |
1300 |