Statcom Active Power Fillter

Price:
delixi.au@gmail.com
Weight:
300.00 KGS
Bookmark and Share


Product Description

 

n  Instantaneous and step less dynamic reactive power compensation (power factor or voltage control) and harmonics negation

 

 Untitled_1.jpg


Low voltage statcom (SVG) and power filter helps improve power quality, reduce power losses and lowers environmental impact whilst maintain set point power factor or voltage control. The result is compliance with regulations, increased electrical system capacity, and reduction in maintenance costs.

Instantaneous (<1 cycle response time), dynamic and step less  reactive power compensation based on voltage sourced convertor (VSC) power electronics  technology. Operates dynamically to compensate fast varying capacitive, inductive, unbalanced loads and removal of system harmonics.

Voltage source convertors produces a three phase AC voltage from a DC voltage source, the pulse width modulated AC voltage is coupled to the source voltage by a reactor. By varying the magnitude of the VSC terminal voltage reactive power exchange takes place between the VSC and the AC source (grid supply). If the magnitude of VSC is more than the AC source voltage, capacitive current flows from the source to VSC and the LV statcom generates capacitive reactive power. If the magnitude of the VSC is less then the AC source voltage, inductive current flows from the AC source and the LV statcom produces inductive reactive power.

LV statcom compensates negative sequence currents caused by unbalanced loads and the source will be totally relieved of from negative sequence currents and reactive power resulting in balanced flow of real current in all three phases.

Applications

ü  Highly inductive or capacitive loads 

ü  Unbalanced loads 

ü  Fluctuating loads 

ü  Harmonics negation to comply with regulatory standards 

ü  Loads fed by weak networks 

ü  Power factor control to comply with regulatory standards 

Benefits

ü  Improved power quality

ü  Lower system demand

ü  Increased energy efficiency

ü  Lower system losses

ü  Reduced carbon footprint

ü  No risk of harmonic amplification

ü  Easy installation

Typical Installations

ü  Installations requiring improved power factor

ü  Installations with voltage stability of flicker problems

ü  Installations with motor drives, rectifiers ect causing harmonic injections

ü  Welding factories

ü  Process industries

ü  Pulp and paper mills

ü  Compressor loads

ü  Shipyards

Modular Construction

LV statcom is available in wall or floor mounted units.

Wall mounted units are available in capacities up to 100KVAR per unit. Additional units up to a total of 12 units can be added operating as slaves from a unit dedicated as a master by means of simple configuration of the the menu driven controller.

 wall_mounted_unit.jpg

 

 

Floor mounted cabinets are our unique modular construction with rack mounted power modules that are “plug in”. No additional hardware or software changes are required to add or remove power modules. Power modules are available in 33KVAR or 100KVAR modules, six units of 33KVAR or three 100KVAR modules can be fitted to a single floor standing cabinet. Up to 12

 Floor_mounted_unit.jpg

power modules are operated from a single control unit offering capacity of 366KVAR (33kvar power module) and 1200KVAR (100KVAR power module). If further capacity is required up to 12 units can be simply configured as master/ slave units.

Failure of any module will not affect the overall operation of the LV statcom, unit will continue to operate as normal with reduced capacity of the failed unit.

Individual module status data and system data is displayed in the HMI screen. Advanced automatic soft start features make operation fully standalone and automatic. If grid supply fails the unit will start normal operation automatically when the grid supply returns and conditions are normal.

Resources of the LV statcom can be allocated on a priority basis between power factor control and harmonics negation or voltage control and harmonics negations

 

 

3 Phase 3 wire system 

3 Phase 4 wire system 

Rated compensation current

50A - 400A

50A - 400A

Power supply 

Network VoltageV 

400V-20% ~ +15%

690V-20% ~ +15%

400V-20% ~ +15%

690V-20% ~ +15%

Operating FrequencyHz 

50 / 60± 5%

50 / 60± 5%

Performance indicators 

Filter rate 

THDI<3%(rated)

THDI<3%(rated)

Filter range 

2~50th harmonic, Eliminates all selected harmonics

2~50th harmonic, Eliminates all selected harmonics

Single harmonic compensation adjustment

Adjustable individual harmonic capacity

Adjustable individual harmonic capacity

Transient response time

(Reaction Time)

< 100us

< 100us

Full response time

(Completion of compensation)

< 10ms

< 10ms

Active power loss

< 3%(rated)

< 3%(rated)

Correction of

Three phase imbalance

has

has

Reactive power compensation

Set point power factor

Set point power factor

Overload protection

Automatic current limiting

at 100% of rated output

Automatic current limiting

at 100% of rated output

Switching frequency

20KHz

20KHz

Display and operation 

Screen mode 

5.7 inch touch screen

5.7 inch touch screen

Display status 

Electrical network parameters

such as voltage and current

Electrical network parameters

such as voltage and current

Communications 

Modbus,RS485,RS232

Modbus,RS485,RS232

Product Location 

Location mode 

Wall mounted cabinet

Floor standing cabinet

Wall mounted cabinet

Floor standing cabinet

Parallel mode 

12 units in parallel

12 units in parallel

Environmental conditions 

Environmental temperature

-10~45

-10~45

Storage temperature

-40~65

-40~65

Relative humidity 

Maximum 95%

Maximum 95%

Altitude 

Less than 1000m

Less than 1000m

 

 

Statcom performance video displaying power factor correction and harmonics negation, dynamically and instantaneous